Leave Your Message

GV4LE03S Motor circuit breaker, TeSys GV4, TeSys GV4, 3P, 3.5A, Icu 100kA, magnetic, EverLink terminals acb electrical

GV4LE03S

jius2.jpg

  • model1 GV4LE03S

Manufacturer: Schneider Electric

[In] rated current: 3.5A

Product or Component Type: Motor circuit breaker

Description

The TeSys GV motor circuit breaker is a 3-pole (3P) device rated at 3.5A/690V, specifically designed for protecting 3-phase motors ranging from 0.55 to 1.5kW at 400V. It offers magnetic protection with a breaking capacity of Icu 100kA at 400V, and features start-stop control via a toggle switch. The breaker connects using Everlink BTR screw terminals. The magnetic protection is adjustable via a dial, with a setting range of 6-14 In. Additionally, internal space is provided for the installation of auxiliary contact blocks (OF, SD) and voltage trip units (MN, MX). For complete motor protection, this circuit breaker should be used in conjunction with a class 10 or 20 thermal overload relay. It is certified to multiple standards (IEC, CCC, EAC, Marine) and complies with the Green Premium program (RoHS/REACH).

Specifications

Main

Product name
TeSys GV4
TeSys Deca
Product or component type Motor circuit breaker
device short name GV4P
Device Application Motor protection
Trip unit technology Thermal-magnetic
Poles description 4P
Fixing mode
35 mm symmetrical DIN rail: clipped
Panel: screwed (with 2 x M4 screws)
Motor power kW
0.55 kW at 400...415 V AC 50/60 Hz
0.75 kW at 400...415 V AC 50/60 Hz
0.75 kW at 500 V AC 50/60 Hz
1.1 kW at 500 V AC 50/60 Hz
1.1 kW at 660...690 V AC 50/60 Hz
1.5 kW at 660...690 V AC 50/60 Hz
1.5 kW at 500 V AC 50/60 Hz
2.2 kW at 660...690 V AC 50/60 Hz
1.1 kW at 400...415 V AC 50/60 Hz
Breaking capacity
120 kA Icu at 220...240 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 380...415 V AC 50/60 Hz conforming to IEC 60947-2
70 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
18 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 660...690 V AC 50/60 Hz conforming to IEC 60947-2