Manufacturer: Schneider Electric

Thermal protection adjustment range: 0.1…0.16 A

Product compatibility: LC1D25-38

Thermal overload class: Class 10A IEC 60947-4-1

Description

The LRD01 is a TeSys LRD thermal overload relay from Schneider Electric, designed for use with TeSys D contactors. It effectively protects motors less than 0.06kW at 400V, featuring a thermal setting range of 0.10-0.16A, tripping class 10A, and phase unbalance protection. 
This relay is intended for direct mounting on TeSys D contactors, ensuring seamless integration and compact assembly. It offers manual test and reset buttons, an automatic reset option, and includes trip auxiliary contacts and a flag indicator for status monitoring. The device is multi-standards certified (IEC, UL, CSA, CCC, EAC, Marine) and Green Premium compliant, adhering to RoHS and REACH standards.
The LRD01 thermal overload relay is a bimetallic type, providing phase unbalance protection for enhanced motor safety. It mounts directly on the bottom terminals of TeSys contactors LC1D09-D38, forming a compact motor starter. The relay is light and compact, with a width of just 45mm, and is temperature compensated for accurate protection.

Specifications

Main

Product name TeSys LRD
Product or component type Differential thermal overload relay
device short name LRD
Device Application Motor protection
Product Compatibility
LC1D09
LC1D12
LC1D18
LC1D25
LC1D32
LC1D38
Thermal overload class Class 10A IEC 60947-4-1
Thermal protection adjustment range
0.1...0.16 A
[Ui] rated insulation voltage 
Power circuit 600 V CSA
Power circuit 600 V UL
Power circuit 690 V IEC 60947-4-1
Auxiliary contact composition
1 NO + 1 NC