Contactor, TeSys Deca, 3P(3 NO), AC-3/AC-3e,
Manufacturer: Schneider Electric
Rated current@AC-3/AC-3e 440 V: 50A
Rated power 460/480V 50/60Hz 3-phase: 40HP
[Uc] control circuit voltage: 400VAC
The TeSys D contactor is a robust 3-pole (3NO) device specifically designed for motor control applications. With a rating of up to 50A/440V AC-3/3e (22kW@400V), it offers exceptional performance in demanding industrial settings. Its 400V 50/60Hz AC coil ensures smooth and reliable operation, while the built-in 1NO+1NC auxiliary contacts (with NC mirror certification) provide added flexibility and control.
The contactor features EverLink BTR screw connectors for power connection, ensuring secure and efficient wiring. Control connection is simplified with screw clamp terminals, making setup and maintenance straightforward. With an operational capacity of up to 3600 cycles per hour and a temperature tolerance of up to 60°C, the TeSys D contactor demonstrates high reliability and durability.
The compact design (55mm width) allows for easy installation, and it offers both DIN-rail and screw fixing options for mounting flexibility. The contactor is certified by multiple standards bodies, including IEC, UL, CSA, CCC, EAC, and Marine, ensuring compliance with international safety and performance standards. Additionally, it is Green Premium compliant, adhering to RoHS and REACh regulations for environmental protection.
Overall, the TeSys D contactor is a high-performance, feature-rich solution for motor control applications. Its robust design, reliable performance, and compliance with multiple standards make it a top choice for industrial motor control systems.
Main
Range of product | TeSys Deca |
Product or component type | Contactor |
device short name | LC1D |
contactor application | Motor control Resistive load |
utilisation category | AC-4 AC-3 AC-1 AC-3e |
Poles description | 3P |
[Ue]rated operational voltage | Power circuit:<=690 V AC 25...400 Hz Power circuit:<=300 V DC |
[le]rated operational current | 50 A (at <60 °C) at <= 440 V AC AC-3 for power circuit
80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit
50 A (at <60 °C) at <= 440 V AC AC-3e for power circuit
|
[Uc]control circuit voltage | 400VAC 50/60 Hz |