Leave Your Message

Motor circuit breaker, TeSys Deca, 3P, 24 to 32A, thermal magnetic, screw clamp terminals, rotary handle

GV2P32

jius2.jpg

  • model1 GV2P32

Manufacturer: Schneider Electric

[In] rated current: 32A

Breaking capacity: 50 kA Icu at 400/415 V AC 50/60 Hz IEC 60947-2

Description

The TeSys GV motor circuit breaker, rated at 32A/690V and designed for 3-phase motor applications up to 15kW@400V, features a 3-pole (3P) configuration. It offers dependable thermal-magnetic protection with a thermal setting range of 24-32A and magnetic tripping at 13 times the nominal current (13xIn). The device has a high breaking capacity of 50kA@400V. Connections are made via screw clamp terminals. It includes a rotary knob for start-stop control, guaranteed for 100,000 cycles under AC-3 conditions. This circuit breaker is certified by multiple international standards (IEC, UL, CSA, CCC, EAC, Marine, ATEX) and is Green Premium compliant, meeting RoHS and REACh directives.

Specifications

Main

Product name TeSys GV2
Product or component type Motor circuit breaker
device short name GV2P
Device Application Motor protection
Trip unit technology Thermal-magnetic
Poles description 3P
Fixing mode
35 mm symmetrical DIN rail: clipped
Panel: screwed (with 2 x M4 screws)
Motor power kW
15 kW at 400/415 V AC 50/60 Hz
18.5 kW at 500 V AC 50/60 Hz
22 kW at 690 V AC 50/60 Hz
Breaking capacity
100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
4 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2