Leave Your Message

Motor circuit breaker, TeSys Deca, 3P, 17 to 23A, thermal magnetic, screw clamp terminals, rotary handle

GV2P21

jius2.jpg

  • model1 GV2P21

Manufacturer: Schneider Electric

[In] rated current: 23A

Breaking capacity: 50 kA Icu at 400/415 V AC 50/60 Hz IEC 60947-2

Description

The TeSys GV motor circuit breaker, designed with 3 poles (3P) and a rating of 23A/690V, is ideal for 3-phase motor applications up to 9kW at 400V. This device provides comprehensive thermal-magnetic protection with a thermal setting range of 17-23A and magnetic tripping at 13 times the nominal current (13xIn). It features a high breaking capacity of 50kA at 400V. Connections are made using secure screw clamp terminals. The circuit breaker is equipped with a rotary knob for start-stop control, which is rated for 100,000 operations under AC-3 conditions. It is certified to various international standards, including IEC, UL, CSA, CCC, EAC, Marine, and ATEX, and meets Green Premium criteria, ensuring compliance with RoHS and REACh directives.

Specifications

Main

Product name TeSys GV2
Product or component type Motor circuit breaker
device short name GV2P
Device Application Motor protection
Trip unit technology Thermal-magnetic
Poles description 3P
Fixing mode
35 mm symmetrical DIN rail: clipped
Panel: screwed (with 2 x M4 screws)
Motor power kW
9 kW at 400/415 V AC 50/60 Hz
11 kW at 500 V AC 50/60 Hz
18.5 kW at 690 V AC 50/60 Hz
Breaking capacity
100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
4 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2