Motor circuit breaker, TeSys Deca, 3P, 13 to 18A, thermal magnetic, screw clamp terminals, rotary handle
Manufacturer: Schneider Electric
[In] rated current: 18A
Breaking capacity: 50 kA Icu at 400/415 V AC 50/60 Hz IEC 60947-2
The TeSys GV motor circuit breaker features a 3-pole (3P) design, rated at 18A/690V, and is ideal for 3-phase motor applications up to 7.5kW@400V. It delivers dependable thermal-magnetic protection, with an adjustable thermal setting range of 13-18A and magnetic tripping at 13 times the nominal current (13xIn). This breaker has a high breaking capacity of 50kA@400V. Connections are secured using screw clamp terminals. It includes a rotary knob for start-stop control, rated for 100,000 cycles under AC-3 conditions. The circuit breaker is certified according to multiple international standards (IEC, UL, CSA, CCC, EAC, Marine, ATEX) and complies with Green Premium standards, meeting RoHS and REACh directives.
Main
Product name | TeSys GV2 |
Product or component type | Motor circuit breaker |
device short name | GV2P |
Device Application | Motor protection |
Trip unit technology | Thermal-magnetic |
Poles description | 3P |
Fixing mode | 35 mm symmetrical DIN rail: clipped
Panel: screwed (with 2 x M4 screws)
|
Motor power kW |
7.5 kW at 400/415 V AC 50/60 Hz
9 kW at 500 V AC 50/60 Hz
15 kW at 690 V AC 50/60 Hz
|
Breaking capacity |
100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
4 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
|