Motor circuit breaker, TeSys Deca, 3P, 6 to 10A, thermal magnetic, screw clamp terminals, rotary handle

GV2P14

jius2.jpg

  • model1 GV2P14

Manufacturer: Schneider Electric

[In] rated current: 10A

Breaking capacity: 100 kA Icu at 400/415 V AC 50/60 Hz IEC 60947-2

Description

TeSys GV motor circuit breaker - 3 poles 3P - 10A/690V - for 3 - phase motor applications 3 - 4kW 400V It provides a thermal - magnetic protection with a thermal setting range 6 - 10A - magnetic tripping at 13xIn - high breakTeSys GV motor circuit breaker, 3 poles (3P), 10A/690V, for 3-phase motor applications 3-4kW@400V. It provides a thermal-magnetic protection with a thermal setting range 6-10A, magnetic tripping at 13xIn, high breaking capacity Icu 100kA@400V. Connection by screw clamp terminals. Start-stop control by rotary knob guaranteed for 100 000 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).

Specifications

Main

Product name TeSys GV2
Product or component type Motor circuit breaker
device short name GV2P
Device Application Motor protection
Trip unit technology Thermal-magnetic
Poles description 3P
Fixing mode
35 mm symmetrical DIN rail: clipped
Panel: screwed (with 2 x M4 screws)
Motor power kW
3 kW at 400/415 V AC 50/60 Hz
5 kW at 500 V AC 50/60 Hz
5.5 kW at 690 V AC 50/60 Hz
Breaking capacity
100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
6 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2