Motor circuit breaker, TeSys Deca, 3P, 2.5 to 4A, thermal magnetic, screw clamp terminals, rotary handle
Manufacturer: Schneider Electric
[In] rated current: 4A
Breaking capacity: 100 kA Icu at 400/415 V AC 50/60 Hz IEC 60947-2
TeSys GV motor circuit breaker - 3 poles (3P) - 4A/690V - for 3-phase motor applications 1.1-1.5kW@400V. It provides thermal-magnetic protection with a thermal setting range of 2.5-4A and magnetic tripping at 13 times the nominal current (13xIn). The device features a high breaking capacity of 100kA@400V and screw clamp terminals for secure connections. Start-stop control is facilitated by a rotary knob, guaranteed for 100,000 cycles under AC-3 conditions. It is certified to multiple standards (IEC, UL, CSA, CCC, EAC, Marine, ATEX) and is Green Premium compliant (RoHS/REACh).
Main
Product name | TeSys GV2 |
Product or component type | Motor circuit breaker |
device short name | GV2P |
Device Application | Motor protection |
Trip unit technology | Thermal-magnetic |
Poles description | 3P |
Fixing mode | 35 mm symmetrical DIN rail: clipped
Panel: screwed (with 2 x M4 screws)
|
Motor power kW |
1.1 kW at 400/415 V AC 50/60 Hz
1.5 kW at 500 V AC 50/60 Hz
2.2 kW at 690 V AC 50/60 Hz
|
Breaking capacity | 100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
100 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2
|