TeSys Deca Manual Starter and Protector, thermal magnetic circuit protector, rotary handle, 0.16…0.25 A, screw clamp terminals
Manufacturer: Schneider Electric
[In] rated current: 0.25A
Breaking capacity: 100 kA Icu at 400/415 V AC 50/60 Hz IEC 60947-2
The TeSys GV motor circuit breaker is a 3-pole (3P) unit rated at 0.25A/690V, ideal for 3-phase motor applications up to 0.06kW at 400V. It includes thermal-magnetic protection with a thermal setting range of 0.16-0.25A and magnetic tripping at 9 times the nominal current (9xIn). It features a high breaking capacity of 100kA at 400V and connects using screw clamp terminals. Start-stop control is managed by a rotary knob, certified for 100,000 AC-3 cycles. The breaker meets multiple certification standards (IEC, UL, CSA, CCC, EAC, Marine, ATEX) and is Green Premium compliant (RoHS/REACH).
Main
Product name | TeSys GV2 |
Product or component type | Motor circuit breaker |
device short name | GV2P |
Device Application | Motor protection |
Trip unit technology | Thermal-magnetic |
Poles description | 3P |
Fixing mode | 35 mm symmetrical DIN rail: clipped
Panel: screwed (with 2 x M4 screws)
|
Breaking capacity | 100 kA Icu at 230/240 V AC 50/60 Hz IEC 60947-2
100 kA Icu at 400/415 V AC 50/60 Hz IEC 60947-2
100 kA Icu at 440 V AC 50/60 Hz IEC 60947-2
100 kA Icu at 500 V AC 50/60 Hz IEC 60947-2
100 kA Icu at 690 V AC 50/60 Hz IEC 60947-2
|