Leave Your Message

Motor circuit breaker, TeSys Deca, 3P, 9 to 14A, thermal magnetic, screw clamp terminals, button control

GV2ME16

jius2.jpg

  • model1 GV2ME16

Manufacturer: Schneider Electric

[In] rated current: 14A

Breaking capacity: 15 kA Icu at 400/415 V AC 50/60 Hz IEC 60947-2

Motor power kW: 5.5 kW at 400/415 V AC 50/60 Hz

Description

TeSys GV motor circuit breaker, 3 poles (3P), 14A/69V, for 3-phase motor applications 5.5kW@4V. It provides a thermal-magnetic protection with a thermal setting range 9-14A, magnetic tripping at 13xIn, high breaking capacity Icu 15kA@4V. Connection by screw clamp terminals. Start-stop control by push-button guaranteed for 1 cycles AC-3. Multi standards certified (IEC, UL, CSA, CCC, EAC, Marine, ATEX), Green Premium compliant (RoHS/REACh).

Specifications

Main

Product name TeSys GV2
Product or component type Motor circuit breaker
device short name GV2ME
Device Application Motor protection
Trip unit technology Thermal-magnetic
Poles description 3P
Fixing mode
35 mm symmetrical DIN rail clipped
Panel screwed with adaptor plate)
[In] rated current
14A
Motor power kW
5.5 kW at 400/415 V AC 50/60 Hz
Breaking capacity
100 kA Icu at 230/240 V AC 50/60 Hz conforming to IEC 60947-2
15 kA Icu at 400/415 V AC 50/60 Hz conforming to IEC 60947-2
8 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
6 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
3 kA Icu at 690 V AC 50/60 Hz conforming to IEC 60947-2