Circuit breaker PowerPacT L 400A 3 pole 600VAC 18kA I-Line Micrologic 3.3 80% ABC
Manufacturer: Schneider Electric
Device short name: PowerPact H
Poles description: 3P
Breaking capacity code:G
[Uimp] rated impulse withstand voltage: 8 kV IEC 60947-2
Line Rated Current: 400 A
PowerPacT L-Frame circuit breakers are designed to protect electrical systems from damage caused by overloads and short circuits. PowerPacT L-Frame circuit breakers are available with electronic trip units. All PowerPacT L-Frame circuit breakers are equipped with dual-break rotating contacts that reduce the amount of peak current during a short circuit fault. All PowerPacT circuit breakers have an integral push-to-trip button in the cover to manually trip the circuit breaker. PowerPacT L circuit breakers are available in 3 and 4-pole unit mount, I-Line, and drawout constructions. This PowerPacT L, 400A, 3 pole, circuit breaker has an interrupting rating of 18kA at 600VAC. This circuit breaker provides MicroLogic Standard with a 3.3 trip unit and an LI function. This unit has I-Line terminations on the line side and mechanical lugs on the load side. This circuit breaker has a continuous current rating of 80% with an ABC phase connection. PowerPacT L circuit breakers comply to UL, CSA, NOM, and IEC standards and are CE marked.
Main
Product name | PowerPact H |
Device short name | LGA36 |
Product or component type | Circuit breaker |
Device application | Distribution |
Poles description | 3P |
Protected poles description | J |
[In] rated current | 400 A |
[Ue] rated operational voltage | 690 V AC 50/60 Hz IEC 60947-3 |
[Icu] rated ultimate short-circuit breaking capacity | 65 kA 220/240 V AC 50/60 Hz IEC 60947-2
35 kA 380/440/415 V AC 50/60 Hz IEC 60947-2
18 kA 500/525 V AC 50/60 Hz IEC 60947-2
20 kA 250 V DC IEC 60947-2
20 kA 500 V DC IEC 60947-2
|
Performance level | 36 kA |
Trip unit technology | Thermal-magnetic |