Leave Your Message

Circuit breaker ComPacT NSX160F, 36kA at 415VAC, TMD trip unit 80A, 4 poles 3d

C16F6TM080

jius2.jpg

  • model1 C16F6TM080

Manufacturer: Schneider Electric

Device short name: NSX160F

Poles description: 4P

Protected poles description: 3D

[In] rated current: 80 A at 40 °C

Performance level: F 36 kA 415 V AC

Trip unit name: TM-D

Description

The ComPacT NSX160F is a comprehensive 4P 3D fixed circuit breaker that has been designed to maximize space utilization and breaking capacity. It serves as an excellent choice for both standard and specialized applications. Boasting a breaking capacity (Icu) of 36kA rms at 415VAC 50/60Hz, it can handle operational voltages of 690VAC 50/60Hz with ease.This product incorporates a thermal-magnetic trip unit (TMD) with an 80A rating. The TMD trip unit offers adjustable thermal overload protection and fixed magnetic protection, providing comprehensive safety features. The 4-pole version, measuring 140mm x 161mm x 86mm, is available with a range of optional functions and accessories, allowing for customized solutions.The ComPacT NSX160F is compliant with international standards such as IEC 60947, CCC, EAC, and marine specifications, ensuring its reliability and safety in various environments. As part of Schneider Electric's EcoStruxure Power architecture, this breaker represents the pinnacle of efficient and intelligent circuit protection.

Specifications

Main

Product name ComPacT NSX new generation
Device short name NSX160F
Product or component type Circuit breaker
Device application Distribution
Poles description 4P
Protected poles description 3D
[In] rated current 80 A at 40 °C
[Ue] rated operational voltage 690 V AC 50/60 Hz
[Icu] rated ultimate short-circuit breaking capacity
85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
35 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
22 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
8 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
35 kA at 480 V AC 50/60 Hz conforming to UL 508
Performance level F 36 kA 415 V AC
Trip unit name TM-D