Motor circuit breaker, TeSys Deca, 3P, 13 kusvika 18A, thermal magnetic, screw clamp terminals, rotary mubato
Mugadziri:Schneider Electric
[Mu] yakayerwa ikozvino:18A
Kutyora kugona:50 kA Icu pa 400/415 V AC 50/60 Hz IEC 60947-2
Iyo TeSys GV mota yedunhu breaker inoratidzira 3-pole (3P) dhizaini, yakayerwa pa18A/690V, uye yakanakira 3-phase motor applications kusvika 7.5kW@400V. Iyo inopa yakavimbika yekupisa-magineti dziviriro, ine inochinjika yekupisa yekuseta renji ye13-18A uye magineti inofamba kanokwana gumi nenhatu yazvino (13xIn). Iyi breaker ine high breaking capacity inosvika 50kA@400V. Kubatanidza kunochengetedzwa uchishandisa screw clamp terminals. Inosanganisira knob inotenderera yekutanga-yekumira kutonga, yakatemerwa 100,000 cycles pasi pe AC-3 mamiriro. Iyo yedunhu inotyora inobvumidzwa zvinoenderana neakawanda epasirese mwero (IEC, UL, CSA, CCC, EAC, Marine, ATEX) uye inoenderana neGreen Premium zviyero, kusangana neRoHS uye REACh mirairo.
Main
Product name | TeSys GV2 |
Chigadzirwa kana chikamu chemhando | Motor circuit breaker |
mudziyo zita pfupi | GV2P |
Device Application | Dziviriro yemotokari |
Trip unit teknolojia | Thermal-magnetic |
Poles tsananguro | 3P |
Kugadzirisa maitiro | 35 mm symmetrical DIN njanji: yakachekwa Panel: screwed (ine 2 x M4 screws) |
Motokari simba kW | 7.5 kW pa400/415 V AC 50/60 Hz 9 kW pa500 V AC 50/60 Hz 15 kW pa690 V AC 50/60 Hz |
Kuputsa simba | 100 kA Icu pa 230/240 V AC 50/60 Hz inoenderana neIEC 60947-2 50 kA Icu pa 400/415 V AC 50/60 Hz inoenderana neIEC 60947-2 20 kA Icu pa 440 V AC 50/60 Hz inoenderana neIEC 60947-2 10 kA Icu pa500 V AC 50/60 Hz inoenderana neIEC 60947-2 4 kA Icu pa690 V AC 50/60 Hz inoenderana neIEC 60947-2 |